The technical performance of some wind farm equipment does not meet the grid connection safety requirements (2)


Release time:

2018/12/18

Some wind farms' reactive power compensation devices do not meet the grid operation requirements

  Some wind farms' reactive power compensation devices do not meet the grid operation requirements

  First, most wind farm wind turbines do not have the ability to dynamically adjust reactive power, or the capacity configuration and adjustment rate of the dynamic reactive power compensation device do not meet the grid operation requirements. Second, some wind farms have not installed reactive power compensation devices, or most of the reactive power compensation equipment configured in the early stage uses fixed capacitor (reactor) groups, which require manual input and output, and cannot achieve automatic voltage adjustment. Third, the wind turbines have limited ability to participate in system voltage regulation. At present, most wind turbines adopt a constant power factor (mostly 1.0) operation mode. The wind and solar hybrid controller of the wind turbine monitoring system configured by the manufacturer is not open to users or does not have the power factor in-system adjustment function. The unit's voltage regulation ability cannot be effectively exerted, increasing the difficulty of system reactive power regulation, resulting in excessive reactive power configuration in some wind farms.