Wind farm design and construction defects and equipment quality issues pose hidden dangers to production and operation (1)
Release time:
2018/12/18
First, the 35 kV collection system of some wind farms simply applies the conventional distribution network design without standardization, the grounding method is not selected reasonably, and the line selection of single-phase faults cannot be quickly cut off, which is easy to cause the accident to expand and cause the wind turbine to be disconnected from the grid. Second, the wind turbine step-up transformer follows the design and selection principles of the distribution network, a large number of box-type transformers are used, and cable terminals are used too much.
Some wind farms have design defects
First, the 35 kV collection system of some wind farms simply applies the conventional distribution network design without standardization, the grounding method is not selected reasonably, and the line selection of single-phase faults cannot be quickly cut off, which is easy to cause the accident to expand and cause the wind turbine to be disconnected from the grid. Second, the wind turbine step-up transformer follows the design and selection principles of the distribution network, a large number of box-type transformers are used, and cable terminals are used too much. Accidents caused by cable terminal failures have become the main factor in wind farm accidents. Second, the installation design of wind turbines in the southeast coastal area does not fully consider the impact of micro-site selection on the safety of wind turbines. The turbulence intensity calculation of the wind turbine position is inconsistent with the actual situation. Under the very full flow caused by the sudden change of the strong typhoon airflow, equipment damage accidents such as wind turbine tower collapse and blade breakage occur.
In addition, there are some problems in the design of some wind farms: the location of the drainage line is unreasonable, and there is a problem of insufficient safety distance from communication cables, knife switch operating rods, etc.; the insulation support and fixing measures of the cable lines are insufficient, and long-term micro-vibration in strong winds can easily cause insulation damage.
keywords
Related News
CONTACT US
Contact Us
Contact Phone:
Company E-mail:
Company Address:
Max Science Park 1201, Tianshi Road, Shushan District, Hefei City
Product Advisory 1